•  128x64 Graphical Display
•  16-bit Flash Micro-controller with Nano Watt XLP Technology
•  4x4 Matrix Keypad
•  Menu Based Operations
•  Expandable upto 72 Zones
•  Inbuilt Real Time Clock
•  Data Logging upto 500 Events
•  All Zones and Hooter can be enable/disable through Keypad
•  Auto Calibration feature
•  Low and High Voltage alert on Display
•  Extra potential free contact for Fire & Fault
•  Trickle & Fast Charging Facility
•  Compatible with any make Smoke & Heat Detector
•  RS 485 Communication for Repeaters
•  Auto Dialer connectivity facility
•  Connectivity provision for Mimic Panel
•  Password facility available for panel monitoring
AC Power: 220v AC, 50Hz 10%
Standby: 24 V DC
Operating Temperature: 0C to 55C
Operating Humidity: 95% (non-condensing)
Zone Operating Condition
Normal Loop Voltage: 23 V to 24 V
Open Threshold Current: 4.4 mA
Short Threshold Current: 35 mA
Fire Threshold Current: 15-35 mA
Alarm Outputs: 1A (24V DC) (Normal)
NB: Hooter output current can be increased as per customer requirement.
Remote Outputs
Fire Contact1 (C,NO,NC): 240v AC/24v DC@ 7 Amp
Fault Contact (C,NO,NC): 240v AC/24v DC@ 7 Amp
Mechanical Specification
Dimension: 495x495x200mm
Weight: 14 Kg (Without Battery)